Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE ENC-G520LE ENC-G810LE ENC-G820LE ENC-G1310LE ENC-G1320LE ENC-G2400LE Standard Non-drain Apiste Việt Nam đại lý Apiste Việt Nam
Danh mục: Apiste Panel Cooling
Mô tả
Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE
Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE
Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 280/300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H590×W200×D250 |
Volume (kg) | 18 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 3.5/3.3 |
Consumption Current/MAX (A) | 3.7/3.8 |
Starting Current (A) | 7.4/7.7 |
Consumption Voltage/Rating (W) | 300/315 |
Consumption Voltage/MAX (W) | 340/370 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 87g |
Noise (dB) | 59/63 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 6 (M6 x L20) |
---|---|
Exhaust Hose | 2m |
INSULOK Tie | 1 |
Washer | 2(M6) |
Spacer | 6 |
Gland | (Length) 2/ (short) 2 |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for AR310LE |
---|---|
External Fan | Air fan for AR310LE |
Filter | ENC-F-64 |
Vaporization Filter | Evaporation filter for AR310LE |
Electrical Board | Substrate for AR310LE |
ENC-G320LE Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 280/300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H590×W200×D250 |
Volume (kg) | 18 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 1.8/1.4 |
Consumption Current/MAX (A) | 2.1/1.9 |
Starting Current (A) | 4.0/4.2 |
Consumption Voltage/Rating (W) | 295/270 |
Consumption Voltage/MAX (W) | 360/355 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 87g |
Noise (dB) | 59/63 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
ENC-G510LE
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 400/500 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H500×W350×D230 |
Volume (kg) | 19 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 3.3/3.0 |
Consumption Current/MAX (A) | 3.6/3.7 |
Starting Current (A) | 7.4/7.7 |
Consumption Voltage/Rating (W) | 270/290 |
Consumption Voltage/MAX (W) | 320/360 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 100g |
Noise (dB) | 63/67 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED / RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G520LE
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 400/500 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H500×W350×D230 |
Volume (kg) | 19 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 1.8/1.4 |
Consumption Current/MAX (A) | 1.9/1.6 |
Starting Current (A) | 4.0/4.2 |
Consumption Voltage/Rating (W) | 280/250 |
Consumption Voltage/MAX (W) | 330/300 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 100g |
Noise (dB) | 63/67 |
External Output | Alarm output(a contact: No-voltage resistive load 250V 2A) |
Display | LED / RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G810LE
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 700/800 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H730×W300×D280 |
Volume (kg) | 26 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 5.7/4.9 |
Consumption Current/MAX (A) | 6.5/6.4 |
Starting Current (A) | 15.6/14.7 |
Consumption Voltage/Rating (W) | 460/470 |
Consumption Voltage/MAX (W) | 590/630 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 240g |
Noise (dB) | 64/68 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G820LE
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 700/800 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H730×W300×D280 |
Volume (kg) | 26 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 2.6/2.3 |
Consumption Current/MAX (A) | 3.2/3.2 |
Starting Current (A) | 7.5/7.1 |
Consumption Voltage/Rating (W) | 440/460 |
Consumption Voltage/MAX (W) | 600/610 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 240g |
Noise (dB) | 64/68 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE
ENC-G1310LE
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 1150/1300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H900×W400×D250 |
Volume (kg) | 36 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 7.5/7.2 |
Consumption Current/MAX (A) | 8.6/9.0 |
Starting Current (A) | 22.3/20.5 |
Consumption Voltage/Rating (W) | 620/690 |
Consumption Voltage/MAX (W) | 770/870 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | R-407c 330g |
Noise (dB) | 68/72 |
External Output | Alarm output(a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G1320LE
Mount Type | Side-mount |
---|---|
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H900×W400×D250 |
Volume (kg) | 36 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 3.3/3.4 |
Consumption Current/MAX (A) | 4.2/4.4 |
Starting Current (A) | 12.7/11.6 |
Consumption Voltage/Rating (W) | 620/700 |
Consumption Voltage/MAX (W) | 805/880 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | R-407c 330g |
Noise (dB) | 68/72 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G2400LE
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 2100/2400 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H1380×W450×D230 |
Volume (kg) | 63 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Three phase AC200 |
Consumption Current/Rating (A) | 5.0/4.6 |
Consumption Current/MAX (A) | 6.7/6.9 |
Starting Current (A) | 31/30 |
Consumption Voltage/Rating (W) | 1220/1410 |
Consumption Voltage/MAX (W) | 1490/1770 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 510g |
Noise (dB) | 70/73 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G810EXE
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 700/800 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H338×W670×D353 |
Volume (kg) | 30 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 5.7/4.9 |
Consumption Current/MAX (A) | 6.6/6.5 |
Starting Current (A) | 15.6/14.7 |
Consumption Voltage/Rating (W) | 470/475 |
Consumption Voltage/MAX (W) | 600/640 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 250g |
Noise (dB) | 60/65 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G820EXE Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 700/800 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H338×W670×D353 |
Volume (kg) | 30 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 2.6/2.3 |
Consumption Current/MAX (A) | 3.2/3.0 |
Starting Current (A) | 7.5/7.1 |
Consumption Voltage/Rating (W) | 435/455 |
Consumption Voltage/MAX (W) | 580/600 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 250g |
Noise (dB) | 60/65 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
ENC-G1310EXE Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 1150/1300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H448×W710×D370 |
Volume (kg) | 44 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 7.2/7.0 |
Consumption Current/MAX (A) | 8.7/9.5 |
Starting Current (A) | 22.3/20.5 |
Consumption Voltage/Rating (W) | 590/680 |
Consumption Voltage/MAX (W) | 770/900 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | R-407c 385g |
Noise (dB) | 65/68 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G1320EXE
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 1150/1300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H448×W710×D370 |
Volume (kg) | 44 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 3.3/3.4 |
Consumption Current/MAX (A) | 4.0/4.4 |
Starting Current (A) | 12.7/11.6 |
Consumption Voltage/Rating (W) | 590/680 |
Consumption Voltage/MAX (W) | 740/870 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | R-407c 385g |
Noise (dB) | 65/68 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | The temperature inside the van / LED error display / RUN LED |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE
Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE ENC-G520LE ENC-G810LE ENC-G820LE ENC-G1310LE ENC-G1320LE ENC-G2400LE Standard Non-drain Apiste Việt Nam đại lý Apiste Việt Nam
xem thêm sản phẩm https://automation.pitesvietnam.com/
Đánh giá (0)
Hãy là người đầu tiên nhận xét “Apiste Panel Cooling Units ENC-G310LE ENC-G320LE ENC-G510LE ENC-G520LE ENC-G810LE ENC-G820LE ENC-G1310LE ENC-G1320LE ENC-G2400LE Standard Non-drain Apiste Việt Nam đại lý Apiste Việt Nam” Hủy
Sản phẩm tương tự
AES 1112.2 SCHMERSAL HÃNG SCHMERSAL VIỆT NAM
308023/303313 KNF , BƠM KNF , ĐẠI LÝ CHÍNH THỨC KNF TẠI VIỆT NAM
Apiste Panel Cooling
F035293 Gefran ,Biến Tần F035293 , Đại lý chính thức Gefran tại Việt Nam
Đánh giá
Chưa có đánh giá nào.