ONICON’s F-2700 Máy Đo lưu lượng xoáy
là một thiết kế linh hoạt ,cung cấpchính xác, đáng tin cậy
đo lưu lượngtrong hơi nước các ứng dụng
APPLICATIONS
• Saturated steam
• Hot w
ater to 500°F (260°C)
Applications with optional pressure sensor
• Superheated steam to 500°F (260°C)
• Compressed air
FEATURES
• Mass flow measurement from a single instrument
• Optional steam energy flow measurement
• Integral 1,000 Ω platinum RTD for precise temperature
measurement
• Optional integral pressure transducer for accurate
pressure readings at the meter location
• DC loop powered operation
• Maintenance free non-moving parts design
• Wear-resistant bluff body/sensor design
• Advanced signal processing algorithms ensure stable
flow readings and reject noise.
• Easy-to-install meter arrives fully programmed and
ready to use.
• Optional multi-analog output versions available
• HART® serial communication
• Optional BACnet MS/TP or MODBUS RTU RS485
serial communication
CALIBRATION
Every ONICON flow meter is wet calibrated in a flow
laboratory against standards that are directly traceable
to NIST.* A certificate of calibration accompanies every
meter.
DESCRIPTION
The ONICON F-2700 Series Insertion Vortex Flow Meter
is a flexible design that delivers accurate, reliable flow
measurement in a wide variety of applications. The integral
temperature sensor and optional integral pressure sensor
allow for direct mass flow measurement in steam and
compensated flow measurement in compressed air and
gases. A volumetric flow version of the meter is also
available for liquid flow applications.
ONICON insertion style vortex meters can be installed
without disrupting flow, making them ideal for retrofit
applications. They are also a cost effective option in larger
pipes as they are priced independent of the pipe diameter.
F-2700 TRANSMITTER F-2700 ONICON Máy Đo lưu lượng F-2700 HÃNG ONICON VIỆT NAM
PERFORMANCE STEAM and GAS ACCURACY
(Reynolds number ≥10,000)
±1% Volumetric flow rate
±1.5% Mass flow rate
LIQUIDS ACCURACY ±0.7% Volumetric flow rate
REPEATABILITY ±0.2%
LONG TERM STABILITY ±0.2% over a period of 1 year
OPERATING
CONDITIONS
AMBIENT TEMPERATURE -40°F to 185°F
PROCESS TEMPERATURE -330°F to 500°F
INPUT POWER AVAILABLE OPTIONS • Loop Power: 12-36 VDC, 25 mA max
• External DC Power: 12-36 VDC, 300 mA max
• External AC Power: 100-240 VAC, 50/60 Hz, 5W max
I/O SIGNAL DC LOOP POWERED One (1) 2-wire, 4-20 mA output
One (1) 2-wire scaled pulse, 50 ms duration, 5 – 36 VDC @ 40 mA
maximum
HART serial communications
EXTERNAL DC or AC
POWERED
Up to three (3) 2-wire, 4-20 mA outputs
One (1) 2-wire scaled pulse output, 50 ms duration, 5 – 36 VDC @ 40
mA maximum
Up to three (3) opto-coupled relay alarm outputs
MODBUS RTU or BACnet MS/TP serial communications
ELECTRONICS
ENCLOSURE
NEMA 4X (IP 66) epoxy painted aluminum
AVAILABLE OPTIONS • Integral mount
• Remote mount (standard cable length 50 ft, maximum 100 ft)
DISPLAY 2-line, 16 character alphanumeric LCD with backlighting option.
APPROVALS SENSING METHOD Class I, Division 1, Group B, C, D
Class II, Division 1, Group E, F, G
Type 4X and IP66, Ta = -40 to 60°C
F-2700 FLOW SENSOR
PERFORMANCE SENSING METHOD Vortex shedding with integral piezoelectric sensors
Integral 1,000 Ω platinum RTD provides instantaneous temperature
Integral pressure transducer (optional) provides instantaneous
pressure.
OPERATING
CONDITIONS
MAXIMUM OPERATING
PRESSURE
≤ Flange rating
PRESSURE LOSS Pressure loss varies with meter size and flow rate. Please contact
ONICON for detailed information